Main distribution frame

From Wikipedia, the free encyclopedia

This is an old revision of this page, as edited by Snafflekid (talk | contribs) at 19:41, 2 March 2007 (format). The present address (URL) is a permanent link to this revision, which may differ significantly from the current revision.

In Telephony, a Main Distribution Frame (MDF or Main Frame) is a signal distribution frame for connecting equipment (inside plant) to cables and subscriber carrier equipment (outside plant). The MDF is a termination point within the local Telephone exchange where exchange equipment and terminations of local loops are connected by jumper wires at the MDF. All copper pairs supplying services through user telephone lines are terminated at the MDF and distributed through the MDF to equipment within the local Exchange e.g. repeaters and DSLAM. Cables to intermediate distribution frames terminate at the MDF. Trunk cables may terminate on the same MDF or on a separate Trunk Main Distribution Frame (TMDF).

The most common kind of large MDF is a long steel rack accessible from both sides. On one side, termination blocks are arranged horizontally at the front of rack shelves. Jumpers lie on the shelves and go through a steel hoop to run vertically to other termination blocks that are arranged vertically. There is a hoop or ring at the intersection of each level and each vertical. Installing a jumper requires two workers, one on each side. The shelves are shallow enough to allow the rings to be within arm's reach, but the workers prefer to hang the jumper on a hook on a pole so their partner can pull it through the ring. A fanning strip at the back of the termination block prevents the wires from covering each others' terminals. With discipined administration the MDF can hold over a hundred thousand jumpers, changing dozens of them every day, for decades without tangling.

For the first half of the 20th Century, all MDF jumpers were soldered. This was reliable but slow and expensive. In the 1960s wire wrap was introduced, and in the 1970s punch blocks.

Each jumper is a twisted pair. Middle 20th century jumper wires in the USA were 24 AWG single strand copper, with a soft polyethylene inner jacket and a cotton wrapper, impregnated to make it slightly brittle and easy to remove neatly. Late 20th century ones had a single, thicker coating of polyethelyne, cross-linked to provide the correct degree of brittleness.

Some urban MDFs are two stories high so they don't have to be more than a city block long. A few are three stories. By British custom the cables to the outside world are terminated on the horizontal side, and the indoors equipment on the vertical side. American usage is vice versa.

Smaller MDFs, and some modern large ones, are single sided so one worker can install, remove or change a jumper. COSMOS and other computerized administrative systems help to keep terminal assignments close to one another, so most jumpers need not be long and the smaller shelves do not become congested. This database keeps track of all terminals and jumpers. In the early and middle 20th century these records were kept as pencil entries in ledger books. The later database method saves much labor by permitting old jumpers to be reused for new lines.

The MDF usually holds central office protective devices and functions as a test point between a line and the office.

Sometimes the MDF is combined with other kinds of distribution frame in a CDF

The MDF in a private branch exchange performs functions similar to those performed by the MDF in a central office.

In order to automate the manual jumpering the Automated Main Distribution Frame (AMDF) becomes an important role.