IEC 60038

From Wikipedia, the free encyclopedia

This is an old revision of this page, as edited by AnomieBOT (talk | contribs) at 19:25, 27 March 2017 (Dating maintenance tags: {{1R}}). The present address (URL) is a permanent link to this revision, which may differ significantly from the current revision.

IEC voltage range AC RMS
voltage
(V)
DC voltage (V) Defining risk
High voltage > 1,000 > 1,500 Electrical arcing
Low voltage 50 to 1,000 120 to 1,500 Electrical shock
Extra-low voltage < 50 < 120 Low risk

International Standard IEC 60038:1983 defines a set of standard voltages for use in low voltage and high voltage AC electricity supply systems.

Low voltage

Where two voltages are given below separated by "/", the first is the root-mean-square voltage between a phase and the neutral connector, whereas the second is the corresponding root-mean-square voltage between two phases (exception: the category shown below called "One Phase", where 240 V is the root-mean-square voltage between the two legs of a split phase). The three-phase voltages are for use in either four-wire (with neutral) or three-wire (without neutral) systems.

Three-phase 50 Hz

  • 230 V / 400 V (formerly 220/380V)
  • 400 V / 690 V (formerly 380/660V)
  • 1000 V (3 wire)

Suppliers using 220 V / 380 V or 240 V / 415 V systems were expected by the standard to migrate to the recommended value of 230 V / 400 V by the year 2003. This migration has already been largely completed, at least within the European Union.

Voltage conversion schedule

Year Neutral-Phase [V] / Phase-Phase [V]
— 1987 220 V / 380 V – 10% .. +10% [1]
1988 — 2003 230 V / 400 V – 10% .. + 6% [1]
2003 — 230 V / 400 V – 10% .. +10% [1]

Three-phase 60 Hz

  • 120 V / 208 V
  • 240 V
  • 277 V / 480 V
  • 480 V
  • 347 V / 600 V
  • 600 V 100

One-phase, three-wire 60 Hz ( American Split-Phase )

  • 120 V / 240 V

Medium voltage

Table 3 of IEC 60038 lists nominal voltages above 1 kV and not exceeding 33 kV. There are two series, one from 3 kV up to 35 kV and another one from 4,16 kV up to 34,5 kV.

High voltage

Table 4 shows nominal voltages above 33 kV and not exceeding 230 kV.

Extra-high voltage

Table 5 is systematically different, as the highest voltage for equipment is the characteristic value exceeding 245 kV. The enumeration begins at 300 kV and ends with 1200 kV.